Technical Support Services  

Clean Rooms


Wafer Fab is housed in immaculately maintained Clean Rooms of about 24,000 sqft comprising of Class 10 to Class 1000. Abutting the Clean Room is an additional un-facilitized space identified for Clean Room expansion. Production support equipment and utilities are housed in Clean Room Sub-Fab.

Clean Room Specifications

The Clean Room contains a segregated diffusion area, etch, photolithography, metallization and Implantation bays. Clean Room laminar airflow is from an ULPA filter ceiling to raised floor, through perforated tiles and through the raised floor space to the side wall air returns.  The air rises to the return air plenum and back to the recirculating air handlers (RAHs) located on the sub-Fab.  Make-up air is mixed in the RAHs before being introduced to the supply air ducts above the ULPA filters.

All services are fed to the Fab from the sub-Fab through the cut outs in Waffle slab and through the raised floor.
 

Clean Room Type = Bay and Chase configuration
Cleanliness specification

=

Class 10 to Class 100 (Class 4 to Class 6 as per ISO 146441)
Ceiling height (Clean Room)

=

10 feet (3.00m)
Raised Floor height

=

2 feet (600mm)
Floor Type

Pedestal and perforated tile
Sub-Fab height

~18 feet (5.4m)
Air velocity at ULPA filter

90 ± 20 fpm
No. of Air changes (designed)

Upto 9/min.
Recovery

< 6 sec.


Clean Room parameters such as temperature, humidity, pressurization are continuously monitored and controlled through a microprocessor based Facilities Control and Monitoring System (FCMS).  A centralized particulate Monitoring Systems constantly monitors the particulate level in the Clean Room.  Regular Testing of the Clean Room is done as per the periodicity stipulated in ISO 146441 to ensure adherence to designed cleanliness level.